| Comet EX RT |
5 kVA |
7 kVA |
11 kVA |
| Performances |
| Active power kVA / kW |
5 / 4 |
7 / 4.9 |
11 / 8 |
| Technology |
on-line double conversion with PFC (Power Factor Correction) system) |
| Rated input voltage |
200/208/220/230/240/250V single phase 380/400/415V three phase |
| Input voltage range |
(-30 %; + 20 %) 230V; (-20 %; + 15 %) 400V; |
| Input, output frequency range |
40-70 Hz, 50/60Hz autoselection, frequency converter as a standard |
| Output voltage / THDU |
200/208/230/240/250V +/- 2%; THDU < 2% |
| Overall eficiency |
normal mode 91%, eco mode 97% |
| THDI |
THDI < 5% |
| Crest factor / short circuit current |
3:1 / 100A |
3:1 / 150A |
| Overload capacity |
>150% 500 ms; 150% 30 s; 125% 60 s; 110% 120 s |
| Temperature operating |
45 C for 8 Hrs, 40 C continous |
| Back-up times at 70% load |
| from 10 up to 15 minutes |
Standard: 1 power mod. 3U + 1 battery mod. EXB 3U = 6U |
| from 15 up to 20 minutes |
Standard + 1 battery mod. EXB 3U = 9U |
| from 40 up to 65 minutes |
Standard + 2 battery mod. EXB 3U = 12U |
| Connection |
| Input / output |
terminal block for 13mm (stranded cable) or 10mm (solid cable) |
| Communication |
| Port type |
6 voltage free contacts DB9 2A 48V dc, 1 RS 232, Rj11 for remote emergency power off |
| Slot |
1 slot for MGE inter-unit communication card |
| Standards and certification |
| Performance and safety |
IEC 62040-1/IEC 60950/UL 1778 and CSA 22.2 |
| EMC |
IEC 62040-2; EN 50091-2; FCC class A, EMC B level |
| Certification |
UL/TUV, GS mark,CB,C-Tick,CE,IEC 68-2-6 (vibration tests marine approval) |
| Dimensions (H X W X D) in mm; weight (single phase input / three phase input) |
| Comet EX RT standard backup tower |
444,5 x 261,2 x 700 |
| |
85,5 Kg |
83,3 Kg / 89,5 Kg |
94,2 Kg / 95,3 Kg |
| Comet EX RT standard backup Network Pack rack mounting |
261,2 (6U) x 444,5 x 700 |
| |
97,3 Kg |
96,1 Kg / 97,3 Kg |
102 Kg / 103,1 Kg |
| Comet EX RT Power module |
444,5 x 130,6 x 650 / 130,6 (3U) x 444,5 x 700 |
| |
24,2 Kg |
23 Kg / 24,2 Kg |
24,9 Kg / 26 Kg |
| Battery module Comet EXB RT |
444,5 x 130,6 x 650 / 130,6 (3U) x 444,5 x 650 |
| |
64,5 Kg |
64,5 Kg |
68,5 Kg |
| EX RT CLA module / EX RT Transformer |
130,6 (3U) x 444,5 x 650 / 12 Kg / 87 Kg |
| Part numbers |
| Ratings |
5 kVA |
7 kVA |
11 kVA |
| Input voltage |
single-phase |
three-phase |
single-phase |
three-phase |
single-phase |
three-phase |
| Comet EX RT standard back-up time Tower |
- |
68 054 |
68 070 |
68 074 |
68 110 |
68 114 |
| Network Pack Rack Format |
- |
68 056 |
68 072 |
68 076 |
68 112 |
68 116 |
| EXB RT battery module / EXB RT battery module with EPO built-in |
- |
68 076 |
68 118 / 68 119 |
Comet EX RT Power module (for use with EXB or CLA module) |
- |
68 057 |
68 057 |
68 077 |
68 115 |
68 117 |
| Rack kit for Comet EX RT Power module / Comet EXB RT and CLA |
- |
68 001 / 68 002 |
| EX RT Transformer module |
- |
68 003 |
| Comet EX RT CLA module (2 to 8 hours) |
- |
68 004 |
| EX RT Battery Integration System |
- |
68 005 |
| EMC B level filter module |
- |
- |
68 008 |
- |
68 008 |
- |
| Comet PDU 19" rack format |
- |
66 857 |
| 1.8m battery connection cable |
- |
68 006 |
| UPS Control, remote UPS monitor display |
- |
66 080 |
|