Rated power (kVA for pf = 0.8) 160 200 250 300 400 500 600 800
Active power (kW) 160 200 250 300 400 500 600 800
Normal AC input
Rated voltage 380 V - 10% to 415 V + 15% - three-phase (1)
Frequency 50 or 60 Hz +/- 5%
Current distortion THDI < 4% with THM filter
Power factor Up to 0.95 with THM filter
Bypass AC input
Voltage 380 V, 400 V or 415 Veff +/- 10% - three-phase + neutral (1)
Frequency 50 or 60 Hz +/- 5%
Output
Phase-to-phase voltages 380 V, 400 V or 415 Veff +/- 1% - three-phase + neutral (1)
Frequency 50 or 60 Hz +/- 0.25%
Permissible overload 150% In for 1 minute, 125% In for 10 minutes
Voltage distortion (THDU) (3) <2% ph/ph, <5%ph/N for linear loads
<3% ph/ph, <5% ph/N for non-linear loads
Short circuit capacity 2.33 In-1 s (2)
Transient voltage variations +/- 5% for 0% to 100% or 100% to 0% step load
Battery characteristics
Backup Time 8, 10, 15, 20, 30, 60 minutes
Type sealed lead-acid (5 or 10 years life)
Input/output efficiency
At 100% load up to 94.5%
At 50% load up to 95%
Environment
Heat losses (3) in kW 8.8 12.4 13.5 16.7 23 24.2 34.5 37.3
Storage temperature range -25C to +45C (with batteries)
Operating temperature range 0C to 35C (40C for eight hours)
Noise level (dBA) <68 <68 <69 <69 <72 <72 <72 <75
Standards
Construction and safety IEC 62040-1, IEC 60950, IEC 50091-1
Performance and topology IEC 62040-3, EN 50091-3
Design and Manufacture ISO 14001, ISO 9001, IEC 60146
EMC IEC 62040-2 and EN 50091-2 level B
Certifications and marking TUV, CE
(1) Other voltages on request: 208, 220, 480 V
(2) 2.33 = 1.67 2 (operation in current-limiting mode for a peak value of 1.67 In). In = rated output current (for pf = 0.8)
(3) The loses indicated are for the cabinets operating at full rated load with the battery float charging.

Dimensions and weight of Galaxy UPS (depth = 840 mm, height = 1900 mm)
Rated power (kVA) 160 200 250 300 400 500 600 800
Width (mm) 1600 1600 1600 1600 1600 3600 3600 4283
Weight (kg) 1500 1500 1650 1650 2030 3500 3500 4560